Note: There are many more startup steps that are NOT included in this quick start guide. Please consult the manufacturer's installation manual for the full startup procedure.
Example chart to verify airflow
You can adjust settings and parameters using the LCD display and joystick on the Simplicity Smart Equipment (SSE) board. However, it's much easier to use the YORK CWa mobile app.
There are two ways get connected to the SSE board with your mobile device
YORK offers a small circuit board that mounts on the SSE board. This can be factory or field installed. This is the same board that must be installed to connect to a BACnet MS/TP bus.
Connection tip: In the SSE board, navigate to the "PIN" menu to reveal the PIN code to enter into your phone. This is located under Controller > Bluetooth > PIN
Comm card outlined in RED above
This service tool plugs into the Ethernet port on the SSE board. Once plugged in, your phone can connect via Bluetooth.
Connection tip: Once the CWCVT is plugged in to the SSE board, press the "A" button a couple times to reveal the "PIN" code that your phone needs to connect (the Pin code is not shown on the picture, but if you press the A button again it will show up).
CWCVT pictured above
The SSE board should arrive factory-programmed for the correct number of stages, fan type, fresh air option, reheat option, etc. However, it is good practice to verify these before startup.
3 options to choose from:
Fixed Variable (IntelliSpeedTM) is the most common setup, so we'll cover some common settings to look at first. First confirm that the fan is set up as Fixed Variable as noted in the previous section.
For Single speed or Fixed Variable, "Thermostat only control" must be set to "YES". This should already be set up if your unit was ordered as IntelliSpeedTM.
💡 Troubleshooting Tip: If thermostat inputs aren't energizing heating/cooling/fan, check this setting first!
In fixed variable, you have the option of selecting different VFD speeds depending on how many cooling or heating stages are being called.
⚠ Caution: Before adjusting speeds for Y and W, make sure that the RTU has been balanced to the correct airflow, so that 100% VFD speed corresponds to the design max airflow.
Note: These settings are ignored by the SSE board if the unit is programmed for Variable fan (VAV)
Here is how to set the leaving air temperature setpoint and return temperature reset points:
Parameter Descriptions
Logic: If the return temperature is above 72°F, the unit targets the VAV Lower setpoint. If the return air temperature is below 72°F, the unit targets the Upper setpoint.
After confirming the fan control type is set to "variable", make sure to set the duct static setpoint.
If your unit will be operating in SZ-VAV mode, make sure to set the occupied cooling and heating set points
For True-VAV or SZ-VAV, a schedule must be set up by either a 3rd party controls contractor (BACnet MS/TP), or a schedule can be programmed in the SSE board.
Economizer Minimum Position: When the RTU is occupied, regardless of heating or cooling calls, the economizer will be at this minimum position (%)
For Dry bulb, go to "Economizer Outdoor Air Temperature Enable Setpoint". We typically recommend setting this to 55°F.
For Enthalpy control, go to "Economizer Outdoor Air Enthalpy Enable Setpoint". We typically recommend setting between 23-25 btu/lb. The lower the number, the less free cooling will be achieved, but also fewer "no cooling" call backs. Note: must have an enthalpy sensor installed to use enthalpy control
If you don't want to lock out mechanical cooling at any ambient temperature, set this point to NO. This will prevent the unit from locking out the compressor in cold temperatures.
Parameter: Set the OAT Cooling Cutout Enabled = NO
If you would like to enable "poor man's" mechanical cooling in low ambient temperatures, enable this point. This feature will cycle the compressors on and off during low ambient temperatures to keep your space cool and the evaporator coil from freezing. This is typically not required if there is an economizer installed.
We call this the "poor man's" low ambient because A) there is no extra cost to add this feature and B) it should only be used in rare occasions when you need some cooling in a comfort cooling application. This shouldn't be used in a process application where cooling is needed most of the year.
If you'd like to lock out the compressor below a certain ambient temperature, you can achieve that here:
AND
In most applications, the equipment will arrive with either a return or space mount relative humidity (RH) sensor that sends an analog signal (communicating) to the SSE board to report the RH. Then, a user would set the desired space/return RH setpoint. The unit would then operate in dehum mode depending on which option is selected below.
If a relative humidity sensor with a dry contact is preferred, this can be accomplished by updating the point "Use DFS for Dehum = yes." The unit cannot be using the dirty filter switch already.
Here is where you select a space or return RH setpoint. If you plan to use the dry contact, your RH setpoint will be adjusted on the dry contact RH sensor.
NOTE: This is the default mode
The only difference between Normal and Alternate mode is when there is a dehum call and a Y1 call.
Hybrid mode enables a second stage of cooling with a dehumidification call. This adds capacity to remove humidity from the air, but it may also lead to over cooling if there is a light sensible load. Hybrid mode combines Alternate mode and Normal mode and selects the appropriate mode in relation to the cooling staged percent command value.
Note: To enable hybrid mode, Alternate Mode must be turned on first.
Tech Service Questions
Call or text: 816-842-5403
Please have the unit model number and serial number handy
Call your local cfm Distributors store:
YORK has a limited labor warranty for the first 60 days from startup on any Norman-built piece of equipment. If you feel you are entitled to labor reimbursement, when you place a warranty parts order, make sure to tell us the model/serial number, startup date, fail date and job address, along with your warranty PO# or job name.