Start Here
The 60-second versionWhat you need to know before you quote
- York WaterSource = FHP. The whole water source heat pump line is built by Florida Heat Pump and sold under the York brand.
- Everything is R‑454B. The entire portfolio — commercial and residential, water-to-air and water-to-water — is R‑454B refrigerant-enabled. R‑454B is an A2L (mildly flammable), which is why refrigerant leak detection now shows up all over the option lists.
- AA and AE are ~85–90% of what you will quote. AA covers ½–6 tons, AE covers 6–30 tons. Learn those two and the rest of the line selects more easily, not less.
- Commercial series start with A. Residential series start with Q. AA/AD/AQ/AK/AE/AB are commercial water-to-air; AH/AW are commercial water-to-water; QA/QD/QQ/QZ are residential water-to-air; QW is residential water-to-water.
- “Front” always means the electrical box side. Every left/right/front/rear callout on water connections, return air and discharge air is referenced off the panel where you access the electrical box. Set that frame of reference first and the rest follows.
- Only commercial units live in the selection software. Residential is quoted off price pages and ordered by emailing the PO. Residential may be added to the software later.
- Standard commercial warranty is 5 years compressor / 1 year parts. Everything you see in the warranty dropdown is on top of that, is net-priced (no multiplier), and only one can be added per unit.
- Extended range (geothermal) is standard on AA. Several other series are listed as “geothermal ready.”
How the new line compares to what it replaced
- AA — equal to, or smaller than, Legacy in most sizes and dimensions.
- AD — equal to, or smaller than, Legacy and CE in most dimensions.
- AQ and QQ — equal to, or smaller than, Legacy in most dimensions.
- QA — equal to, or smaller than, SV in most sizes and dimensions.
Designed for Service — three cabinet features worth selling
- Slide-out blower. Easy serviceability of the blower, and improved access to the entire refrigerant circuit.
- Swing-out electrical box. The electrical box swings out of the way, allowing improved access and easier servicing of the unit.
- Divided electrical box. A separate designated compartment for high and low voltage components, keeping service technicians safer.
Designed for Service
The Portfolio
R-454B · commercial + residentialThe two family trees below are the master map of the line. Commercial splits water-to-air into Compact (AA / AD / AQ) and Large (AK / AE / AB), plus water-to-water Large (AH / AW). Residential splits water-to-air Compact (QA / QD / QQ / QZ Split) and water-to-water Large (QW).
Commercial WSHP Portfolio
| Series | Branch | Capacity sizes | Blower / motor | Compressor | Voltages |
|---|---|---|---|---|---|
| AA | Water-to-Air · Compact | 007–070 | PSC / ECM CT / ECM CA | Single stage (rotary or scroll) | 1&3φ 208V, 265V, 277V, 460V, 575V |
| AD | Water-to-Air · Compact | 007–078 | ECM constant torque / constant airflow | Single or two stage (rotary or scroll) | 1&3φ 208V, 265V, 277V, 460V, 575V |
| AQ | Water-to-Air · Compact | 024–070 | ECM constant torque / constant airflow | Two stage scroll | 1&3φ 208V, 265V, 277V, 460V |
| AK | Water-to-Air · Large | 009–018 | PSC | Single stage rotary | 1φ 208V, 265V |
| AE | Water-to-Air · Large | 072–360 | Belt drive motor | Two stage scroll | 1&3φ 208V, 460V, 575V |
| AB | Water-to-Air · Large | 360–720 | Belt drive motor | High efficiency scroll | 1&3φ 208V, 460V, 575V |
| AH | Water-to-Water · Large | 025–071 | — (no blower) | Single or two stage scroll | 1&3φ 208V, 265V, 460V |
| AW | Water-to-Water · Large | 120–420 | — (no blower) | Single or two stage scroll | 1&3φ 208V, 460V, 575V |
Residential WSHP Portfolio
| Series | Branch | Sizes | Blower | Compressor | Power | ENERGY STAR |
|---|---|---|---|---|---|---|
| QA | Water-to-Air · Compact | 007–070 | PSC | Single stage (rotary/scroll) | 208‑230/1/60 | No |
| QD | Water-to-Air · Compact | 007–070 | ECM const. torque / const. airflow | Single or two stage (rotary/scroll) | 208‑230/1/60 | Yes |
| Water-to-Air · Compact | 024–070 | ECM constant airflow | Two stage scroll | 208‑230/1/60 | Yes | |
| QZ Split | Water-to-Air · Compact | 024–070 | In the paired air handler | Two stage scroll | 208‑230/1/60 | Yes |
| QW | Water-to-Water · Large | 025–122 | — (no blower) | Std scroll, dual-stage refrigerant circuit | 208V 1φ | Yes |
Series at a Glance
Pick the right model fastOne row per series, sorted commercial then residential. Efficiency ranges are the published ground-loop and water-loop COP/EER spans across the size range.
Every series, side by side
| Series | Market | Tons | Type | Blower | Cabinets | Ground loop COP / EER | Water loop COP / EER |
|---|---|---|---|---|---|---|---|
| AA | Commercial | ½–6 | Water-to-Air | PSC or const. torque ECM (const. DDM ECM 018–070) | Vertical / Horizontal | 3.19–3.80 / 14.32–16.20 | 4.47–4.87 / 12.26–15.60 |
| AD | Commercial | ½–6 | Water-to-Air | Const. torque ECM all sizes; const. airflow 015–070 | Vertical / Horizontal / Counterflow | 3.5–3.7 / 15.5–18.5 | 4.3–5.5 / 13.5–16.0 |
| AQ | Commercial | 2–6 | Water-to-Air | Const. torque AND const. airflow ECM, all sizes | Vertical / Horizontal | 3.8–4.4 / 17.0–27.0 | 5.1–6.2 / 15.0–18.5 |
| AK | Commercial | ½–1¼ | Water-to-Air (console) | PSC, all sizes | 48″ standard, 63″ extended | — | — |
| AE | Commercial | 6–30 | Water-to-Air | Belt drive (inverter duty optional) | Vertical / Horizontal | 3.15–4.35 / 14.85–20.25 | 4.2–6.0 / 13.3–17.75 |
| AB | Commercial | 30–60 | Water-to-Air | Belt drive inverter duty | Modular (heavy duty) standard | — | — |
| AH | Commercial | 2–6 | Water-to-Water | — | Cabinet, unit- or remote-mounted control | — | — |
| AW | Commercial | 10–30 | Water-to-Water | — | Cabinet, unit- or remote-mounted control | — | — |
| QA | Residential | ½–6 | Water-to-Air | PSC only | Vertical / Horizontal | 3.19–3.60 / 14.32–14.80 | 4.45–4.70 / 12.26–14.10 |
| QD | Residential | ½–6 | Water-to-Air | Const. torque 007–012; const. airflow 015–070 | Vertical / Horizontal / Counterflow | 3.5–4.1 / 15.7–24.0 | 4.3–5.5 / 13.3–17.0 |
| Residential | 2–6 | Water-to-Air | Const. airflow ECM, all sizes | Vertical / Horizontal | 3.8–4.40 / 17.0–27.0 | 5.1–6.2 / 15.0–18.5 | |
| QZ / AZ Split | Residential | 2–5 | Split (condensing section) | In the JDE air handler | Painted steel, ½″ closed cell foam | — | — |
| QW | Residential | 2–5, 10 | Water-to-Water | — | Cabinet, unit- or remote-mounted control | — | — |
Which series do I pick?
Smallest footprint, most options, most budget-friendly commercial unit ½–6 ton?
AA. It is the compact commercial workhorse — the most compact footprint, the widest option list, and the lowest price point of the commercial compacts. Together with the AE it is roughly 85–90% of everything a rep quotes.
Customer wants a counterflow cabinet?
AD (commercial) or QD (residential). They are the only series offering vertical, horizontal and counterflow cabinet configurations.
Efficiency is the deciding factor on a 2–6 ton commercial job?
AQ. Two-stage scroll on every size, both constant torque and constant airflow ECM available on all sizes, and the highest published numbers of the compacts — up to 27.0 EER ground loop and 6.2 COP water loop.
Perimeter console application, ½–1¼ ton?
AK. 48″ standard cabinet (63″ extended available), unit-mounted or remote-mounted controls, geothermal ready.
6–30 tons?
AE. Belt drive, two parallel refrigerant circuits, refrigerant leak detection standard, and the take-apart construction option that gets a 30-ton vertical through a 36″ doorway.
Above 30 tons?
AB, 30–60 tons. Heavy-duty modular construction is standard, so it also breaks down to fit through a 36″ door.
No air side — the customer needs hot or chilled water?
AH (2–6 ton) or AW (10–30 ton) commercial; QW (2–5 and 10 ton) residential.
Residential job where first cost rules?
QA. PSC blower only and it is not ENERGY STAR rated — and its warranty is the weakest in the residential line, so confirm the customer is fine with that trade before you quote it.
Commercial Water-to-Air
AA · AD · AQ · AK · AE · AB- Available in sizes ½ through 6 ton (007–070)
- Single-stage / single-speed rotary and scroll compressors
- Equal to, or smaller than, Legacy in most sizes and dimensions
- PSC or constant torque ECM blowers — all sizes. Constant DDM ECM on 018 through 070
- Vertical configuration units internally trapped at the factory
- R‑454B refrigerant-enabled
- Extended range (geothermal) standard
- 1&3φ at 208V, 265V, 277V, 460V and 575V
| Ground Loop | Water Loop | |
|---|---|---|
| COP | 3.19 – 3.80 | 4.47 – 4.87 |
| EER | 14.32 – 16.20 | 12.26 – 15.60 |
AA Series
Factory options — AA
- Left or right front water connections
- Top, end blow, or straight through discharge
- Internal electric heat
- Fiberglass or closed cell foam insulation
- 2% leakage compliant closed cell insulation
- Hot gas reheat (HGRH on/off), hot gas bypass (HGBP), or HGRH w/ HGBP
- 50, 75, or 100 VA transformer
- DDC multi-protocol controls
- 100 kA SCCR
- EMS relay
- Blower monitor relay
- Compressor monitor relay
- Pump valve relay
- Boilerless control
- Flow proving switch
- Disconnect switch
- Fire alarm relay / dual power
- Wire to 208V
- Economizer w/ 3-way valve and controls
- Throwaway, MERV 8, or MERV 13 filter
- 2″ or 4″ filter rack
- Available in sizes ½ through 6 ton
- Vertical, horizontal and counterflow cabinet options
- Single-stage (007–018) / single-speed rotary compressors
- Two-stage (024–070) / dual-speed scroll compressors
- Counter flow design
- Equal to, or smaller than, Legacy and CE in most dimensions
- Constant torque ECM blowers — all sizes
- Constant airflow ECM blowers — 015–070
- Vertical configuration units internally trapped at the factory
- R‑454B refrigerant-enabled
- 100 kA SCCR rating available
| Ground Loop | Water Loop | |
|---|---|---|
| COP | 3.5 – 3.7 | 4.3 – 5.5 |
| EER | 15.5 – 18.5 | 13.5 – 16.0 |
AD Series
Factory options — AD
- Left or right front water connections
- Top, end blow, straight through, and bottom discharge
- Internal electric heat (dual point)
- Fiberglass or closed cell foam insulation
- 2% leakage compliant closed cell insulation
- Hot gas reheat (on/off or modulating), hot gas bypass, or HGRH w/ HGBP, heat recovery pkg. (HRP) 024–070
- 75 or 100 VA transformer
- DDC multi-protocol controls
- 100 kA SCCR
- EMS relay
- Blower monitor relay
- Compressor monitor relay
- Pump valve relay
- Boilerless control
- Flow proving switch
- Disconnect switch
- Fire alarm relay / dual power
- Wire to 208V
- Economizer w/ 3-way valve and controls
- Throwaway, MERV 8, or MERV 13 filter
- 2″ or 4″ filter rack
- Available in sizes 2 through 6 ton
- Vertical and horizontal cabinet options
- Two-stage (024–070) / dual-speed scroll compressors
- Equal to, or smaller than, Legacy in most dimensions
- Constant torque ECM blowers — all sizes
- Constant airflow ECM blowers — all sizes
- Vertical configuration units internally trapped at the factory
- R‑454B refrigerant-enabled
- 100 kA SCCR rating available
| Ground Loop | Water Loop | |
|---|---|---|
| COP | 3.8 – 4.4 | 5.1 – 6.2 |
| EER | 17.0 – 27.0 | 15.0 – 18.5 |
AQ Series
Factory options — AQ
- Left or right front water connections
- Top, end blow, straight through discharge
- Fiberglass or closed cell foam insulation
- 2% leakage compliant closed cell insulation
- Hot gas reheat (on/off or modulating), hot gas bypass, or HGRH w/ HGBP, heat recovery pkg. (HRP) 024–070
- 75 or 100 VA transformer
- DDC multi-protocol controls
- 100 kA SCCR
- EMS relay
- Blower monitor relay
- Compressor monitor relay
- Pump valve relay
- Boilerless control
- Flow proving switch
- Disconnect switch
- Fire alarm relay / dual power
- Wire to 208V
- Economizer w/ 3-way valve and controls
- Throwaway, MERV 8, or MERV 13 filter
- 2″ or 4″ filter rack
- Available in sizes ½ through 1¼ tons
- Unit mounted or remote mounted controls
- Single stage, single speed rotary compressors
- Standard 48″ cabinet
- Geothermal ready
- PSC blowers — all sizes
- R‑454B refrigerant-enabled
- 1φ at 208V and 265V
AK Series console
Factory options — AK
- Left or right water connections
- 63″ extended cabinet length
- Fiberglass or closed cell foam insulation
- 75 VA transformer
- ½″ FPT fittings
- DDC multi-protocol controls
- EMS relay
- Blower monitor relay (with RMC)
- Compressor monitor relay
- Pump valve relay
- Flow proving switch
- Fresh air damper (available with sub-base)
- Wire to 208V
- Non-fused disconnect switch
- Available in sizes 6 through 30 ton
- Single stage, single speed scroll compressors on all sizes
- Belt drive motor (inverter duty optional)
- R‑454B refrigerant-enabled
- Front (vertical) or side (horizontal) water connections — no other choice
- Single blower units 6–15 tons; dual blower 20–30 tons
- 2 parallel refrigerant circuits
- Refrigerant leak detection standard (so it does not appear as an option)
- 1&3φ at 208V, 460V and 575V
| Ground Loop | Water Loop | |
|---|---|---|
| COP | 3.15 – 4.35 | 4.2 – 6.0 |
| EER | 14.85 – 20.25 | 13.3 – 17.75 |
AE Series
Factory options — AE
- Top, end blow, rear, front or straight through discharge
- Inverter duty motor
- DuoGuard air coil
- Fiberglass or closed cell foam insulation
- Compressor blanket
- Take apart construction
- 75 or 100 VA transformer
- DDC multi-protocol controls
- VFD
- Rotated blower
- Rotated motor (DE072–DE181 VT)
- EMS relay
- Blower monitor relay
- Compressor monitor relay
- Phase monitor
- Pump valve relay
- Boilerless control
- Flow proving switch
- Fire alarm relay / dual power
- Wire to 208V
- Economizer w/ 3-way valve and controls
- 2″ or 4″ filter rack
Refrigerant circuit options — AE
The AE offers many refrigerant options and combinations:
- Cooling only
- Hot gas bypass
- Hot gas bypass with cooling only
- Hot gas bypass with hot gas reheat (on/off)
- Hot gas reheat (on/off)
- Hot gas reheat with cooling only
- Modulating hot gas reheat
- Modulating hot gas reheat with cooling only
AE horizontal — return air and discharge rules by size
| Model | Return air | Supply / discharge |
|---|---|---|
| AE072, AE096 | Left return air only | Straight thru or end blow |
| AE120, AE150 | Left return air only | Straight thru supply only |
| AE180, AE242 | Left or right return air | Straight thru |
Take-apart construction
- Vertical units only. Adds a split just below the air filter so the unit separates into an air handler section and a condensing section.
- Lets you carry the unit in and fit it through a 36″ doorway — available all the way up through the 30-ton vertical.
- Ships with a nitrogen holding charge to prevent oxidation inside the coils.
- In the field you must braze the two sections back together, connect the electrical, connect the condensate, and recharge the unit with refrigerant.
- Ideal for retrofit applications where the equipment room door is the constraint.
Take-apart construction
- Available in sizes 30 through 60 ton
- Single stage, single speed scroll compressors on all sizes (high efficiency scroll)
- Belt drive inverter duty motor standard
- Side water connections
- R‑454B refrigerant-enabled
- 100 VA transformer
- Heavy-duty modular construction standard
- Shraeder valves for servicing
- 4″ pleated filter bank
- Refrigerant leak detection standard
AB Series
Factory options — AB
- Front, rear or top discharge air
- Cupronickel coax coil
- Fiberglass or closed cell foam insulation
- DDC multi-protocol controls
- VFD
- Economizer w/ 3-way valve and controls
- Fire alarm relay / dual power
- Wire to 208V
- EMS relay
- Blower monitor relay
- Compressor monitor relay
- Phase monitor
- Pump valve relay
- Boilerless control
- Flow proving switch
Modular construction — vertical high (high boy)
- Refrigerant circuits are pre-charged and sealed — no field brazing or recharging like the AE take-apart.
- Water connections between sections have brass couplings for single water connections.
- AB360 ships in two sections and can be further broken down into three: fan section, main heating/cooling section, and economizer/filter bank section.
- AB480–AB720 ship in four sections and break down into six — the same breakdown as the AB360, but twice.
Modular section breakdown
| Sections | AB360 | AB480 | AB600 | AB720 |
|---|---|---|---|---|
| AH sections | 1 | 2 | 2 | 2 |
| Blower sections | 1 | 2 | 2 | 2 |
| Filter sections | 1 | 2 | 2 | 2 |
| Total sections | 3 | 6 | 6 | 6 |
| Sections shipped | 2 | 4 | 4 | 4 |
Water-to-Water
AH · AW · QW- Available in sizes 2 through 30 ton:
- AH — 2–6 tons (capacity sizes 025–071)
- AW — 10–30 tons (capacity sizes 120–420)
- QW — 2–5 and 10 tons, residential (capacity sizes 025–122)
- Two stage, single speed scroll compressors on all sizes
- Side water connections
- R‑454B refrigerant-enabled
- 75 VA transformer (AH) · 100 VA transformer (AW)
- Cabinet configuration with unit-mounted controller or remote controlled
- QW is ENERGY STAR rated, 1φ at 208V, dual-stage refrigerant circuit, coated/painted cabinet
AH / AW / QW
Factory options — AH / AW / QW
- Cupronickel coax coil
- Compressor blanket
- Remote mounted or unit mounted controls
- DDC multi-protocol controls
- Wire to 208V
- Heat recovery package (AH units only)
- EMS relay
- Blower monitor relay
- Compressor monitor relay
- Phase monitor
- Pump valve relay
- Boilerless control
- Flow proving switch
- Refrigerant leak detection
Residential
QA · QD · QQ · QZ Split + JDEResidential units are not in the York selection software. They are quoted off price pages and ordered by emailing the purchase order. York has indicated residential equipment may be added to the software for quotation purposes at a later date.
- Available in sizes ½ through 6 ton
- Single-speed / single-stage rotary and scroll compressors
- PSC blower only
- Vertical configuration units internally trapped at the factory
- R‑454B refrigerant-enabled
- Equal to, or smaller than, SV in most sizes and dimensions
- Slide-out blower (vertical only), swing-out electrical box, divided electrical box
- Not ENERGY STAR rated · 208‑230/1/60 · coated / painted cabinet
| Ground Loop | Water Loop | |
|---|---|---|
| COP | 3.19 – 3.60 | 4.45 – 4.70 |
| EER | 14.32 – 14.80 | 12.26 – 14.10 |
QA Series
Factory options — QA
- Copper or cupronickel coax coil
- DuoGuard evaporator coil
- Left front water connections (only)
- Top or end blow discharge
- Fiberglass insulation
- Available in sizes ½ through 6 tons
- Vertical, horizontal and counterflow cabinet options
- Single-stage (007–018) / single-speed rotary compressors
- Two-stage (024–070) / dual-speed scroll compressors
- Constant torque ECM blowers — 007–012
- Constant airflow ECM blowers — 015–070
- Vertical configuration units internally trapped at the factory
- R‑454B refrigerant-enabled / ENERGY STAR rated
| Ground Loop | Water Loop | |
|---|---|---|
| COP | 3.5 – 4.1 | 4.3 – 5.5 |
| EER | 15.7 – 24.0 | 13.3 – 17.0 |
QD Series
Factory options — QD
- Copper or cupronickel coax coil
- Duo-Guard evaporator coil
- Left front water connections ONLY
- Top, end blow, or bottom discharge
- FG insulation / painted steel cabinet
- Heat recovery pkg. (HRP) 024–070
- Available in sizes 2 through 6 ton
- Vertical and horizontal cabinet options
- Two-stage (024–070) / dual-speed scroll compressors
- Equal to, or smaller than, Legacy in most dimensions
- Constant airflow ECM blowers — all sizes
- Vertical configuration units internally trapped at the factory
- R‑454B refrigerant-enabled
- 100 kA SCCR rating available
- Heat recovery package available for all sizes
| Ground Loop | Water Loop | |
|---|---|---|
| COP | 3.8 – 4.40 | 5.1 – 6.2 |
| EER | 17.0 – 27.0 | 15.0 – 18.5 |
QQ Series
- Available in sizes 2 thru 5 tons
- Only offered in condensing section — there is no packaged version
- Paired with the JDE Premium Air Handler (and the CDM series cased coil)
- Available only in 208‑230 single phase
- Two stage, single speed rotary compressors
- Geothermal ready
- Option for copper or cupronickel coax
- Painted steel cabinet with ½″ closed cell foam
- R‑454B refrigerant-enabled
- Optional refrigerant leak detection sensor
AZ / QZ Split condensing section
- Premium efficiency — up to 20 SEER2, up to 9.5 HSPF2
- All aluminum evaporator coil for superior corrosion resistance
- Constant torque multi-speed ECM blower motor — designed for two-stage operation
- 5, 8, 10, 15, 20 kW electric heat accessory kits available for supplemental or emergency heating needs
- Easy to install — compatible with most standard 24 VAC heat pump thermostats
- Factory-installed TXV
- Condensate drain pan is polymer with UVC inhibitor
- Factory-installed A2L sensor
JDE Premium Air Handler
Factory Option Guide
What each option does & when to pick itThis is the section that keeps you from over-selecting. Reps regularly check every box on the page and then ask why the unit is so expensive — the answer is almost always three or four options nobody on the job actually needs. Every entry below is “what it is, when you need it, what it costs you if you get it wrong.”
Electrical & voltage
Why do some voltages disappear when I change the size?
Voltage availability narrows as capacity goes up. On the compacts you lose the single-phase voltages — and specifically 265V — as you move into 4, 5 and 6 ton.
The unit says “208/230, single and three phase.” Which one ships?
Both of those voltage selections ship from the factory wired for 230 volt. If you know the building is truly 208V, select the Wire to 208V electrical option and it arrives wired that way.
It is not hard to change in the field — you move one wire on the voltage terminal — but doing it 30, 40, 60 or 100 times is real labor and real money. On any sizeable schedule, if you know it is 208V, take the factory option.
How many electrical options can I add?
Up to five per unit. In practice it is rare that a job actually needs all of them, so the cap is seldom a problem.
What are the common ones?
Pump valve relay — opens a valve when the compressor comes on, for either a pump or an external two-way valve. Disconnect switch — a factory-installed disconnect, wired to 208 volt. Leak sensors — the A2L refrigerant leak detection sensor.
A2L refrigerant leak detection — when is it required?
Do units come standard with refrigerant leak sensors?
It depends on the refrigerant charge. By code, anything with more than 64 ounces (4 pounds) of refrigerant requires leak detection. Below 4 lb it is optional and shows up in the electrical options list.
Which models force it?
The AD and AQ at 5 and 6 tons carry roughly 80 ounces, which puts them over the threshold — the sensor is required and the software will not let you complete the selection without it.
You do not have to memorize this. The software prompts you.
How do I tell at a glance whether it is standard or optional?
If you see it in the electrical options list, it is optional. If you do not see it at all, it is standard — already in the unit's bill of materials. On the larger units (AE, AB) refrigerant leak detection is standard, which is why it never appears as a selectable option.
Heat exchanger — copper vs. cupronickel
Which one do I pick?
Copper, about 90–95% of the time on commercial units. Most commercial buildings are closed loop — boiler/tower, chillers, boilers — and the water quality is maintained.
Upgrade to cupronickel only when the loop is open: a pump-and-dump, or an open-loop geothermal system where water quality will not always be maintained. That is where you want the more robust heat exchanger material.
Water connections & the “front of the unit” convention
What does “front” mean?
The front of the unit is the side where you access the electrical box. Everything else — left/right water, left/right return, front/rear discharge — is built off that frame of reference. Set it first and the rest of the configuration reads correctly.
What are my choices by series?
Small package units, ½–6 ton (AA, AD, AQ): front-left or front-right water. Front-left = water on the front of the left side; front-right = front of the right side.
QA and QD (residential): left front water connections only.
AE: vertical units have front water only; horizontal units have side water only. There is no customization on those.
AB and the water-to-water AH / AW / QW: side water connections.
Return air & discharge air
What are the return air choices?
Compacts (AA / AD / AQ): left or right return.
AE vertical: return air changes to back or front — back means opposite the electrical box, front means the same side as the electrical box. AE horizontal keeps left and right.
What are the discharge choices?
Vertical units: top discharge.
Horizontal units: end blow or straight through.
AE vertical: top discharge, plus rear or front — and the choice you get is always opposite your return air. Front return → rear or top supply. Rear return → front or top supply. The software has this built in; you never have to remember it.
What is the actual difference between straight through and end blow?
Straight through cuts straight across the unit — a straight line from return air to supply air across the narrow path.
End blow brings air in one side, turns it 90°, and shoots it out the skinny end of the unit — the end opposite the control box.
Can discharge be changed in the field?
Yes, on horizontal units. If you are stocking straight-through units and a job needs end blow, it converts in the field: about nine steps, laid out clearly in the IOM, roughly ten minutes. You swap some panels and rotate the blower. This is a real advantage for anyone carrying stock.
Fan motor — PSC vs. constant torque vs. constant airflow
- PSC — the standard blower on AA, QA and AK. Lowest cost, most CFM fall-off as static pressure rises.
- Constant torque ECM — about a 10% efficiency boost over PSC, and it holds the blower curve better. As filters load up and static rises, you lose CFM much more slowly than with a PSC.
- Constant airflow ECM — another ~10% efficiency boost over constant torque. The motor actively ramps up and down to maintain the programmed CFM as static pressure increases. Program it for 2,000 CFM and it will still be delivering 2,000 CFM as the filters get dirty.
What about the large units?
On AE, the default is a belt drive motor with an optional inverter duty motor. The inverter duty motor is mandatory if you are taking the factory VFD, and you want it for a field-installed third-party VFD as well. On AB, the belt drive inverter duty motor is standard.
Air coil — standard vs. DuoGuard coated
When do I upgrade to the DuoGuard coil?
When the air quality where the unit lives is less than ideal — coastlines, waste management facilities, sewer facilities, and anywhere the air is more corrosive and harmful to the coil. Standard uncoated is fine everywhere else.
Cabinet construction & insulation
What are the insulation choices?
All units use galvanized steel cabinets. Insulation runs: standard fiberglass → closed cell foam → 2% leakage compliant closed cell foam.
The difference between plain closed cell and the 2% leakage version is a more robust, more thoroughly sealed cabinet: extra insulation around the panels, any gaps, and the screw holes. It goes the extra mile to seal the cabinet up.
What is the compressor blanket for?
Additional sound attenuation. Each insulation option can add the compressor blanket.
How does take-apart construction work?
On AE vertical units only, it adds a split just below the air filter so the unit can be broken apart in the field and fit through a 36″ doorway — all the way up through the 30-ton vertical.
Once it is in place you must braze the two sections back together, connect the electrical, connect the condensate, and recharge the unit with refrigerant. It ships with a nitrogen holding charge to prevent oxidation inside the coils. Great option for retrofits.
On AB, heavy-duty modular construction is standard and the refrigerant circuits stay pre-charged and sealed — no field brazing or recharging. Water connections between sections use brass couplings so the field still sees single water connections.
Refrigerant circuit — and the cooling-only trap
What is standard?
Standard units are heat pumps — heating and cooling. Above that you can add hot gas bypass, hot gas reheat (for dehumidification), HGBP + HGRH combinations, cooling-only, and on the larger units modulating hot gas reheat. There are roughly 15 combinations across the line.
When in doubt, quote a standard heat pump and just jump out the heating call. Yes, you still have a reversing valve and therefore a potential point of failure — but reversing valve failure rates are extremely low, and you keep every future option open.
Transformers — and why DDC greys out
What sizes are available?
50 VA standard on the AA, with 75 and 100 VA options. AD, AQ and AE start at 75 VA. AK is 75 VA. AB and AW are 100 VA. AH is 75 VA.
Why is the DDC option greyed out?
Because certain options require a higher VA transformer — specifically the DDC controls and the waterside economizer. Go back up, select the 100 VA transformer, and the DDC option becomes selectable again. Same story for the economizer.
Water flow control
| Option | What it does | When you want it |
|---|---|---|
| Two-way solenoid valve | An on/off electric valve. Opens when the compressor comes on to allow water in; closes when the compressor is not running. | Variable-flow loops where you want the unit to shut off its own water. |
| MeasureFlow / AFV | A special cartridge in a valve that sets the flow to 3 GPM per ton. | When you want the unit balanced from the factory instead of field-balanced. |
| Water regulating valve connect | Just Schrader valves, so a third-party water regulating valve can be connected. | Only really needed if the unit runs with sub-50°F entering water, which is fairly rare. |
| Flow proving switch | A waterside differential pressure switch that shuts the unit off when it detects very low or no flow — and auto-resets. As soon as flow returns, the switch resets the board and the unit starts running again. | Schools, high-rises, big commercial buildings. Arguably the single best-value option in the list. |
Waterside economizer (free cooling coil)
What is it, physically?
A cold water coil mounted on the outside of the unit for economizer mode. Some people call it a free cooling coil. In the software it appears as “economizer w/ 3-way valve and controls.”
Anything it depends on?
Yes — like the DDC, it requires the 100 VA transformer. It also adds pressure drop, so the standard airflow tables will not exactly match your final performance.
Air filtration & filter racks
Compacts (AA / AD / AQ) — what are my choices?
Standard 1″ throwaway filter, plus MERV 8, MERV 13, and a robust 4″ MERV 13. Filter racks are available in 2″ or 4″.
Side access or bottom access?
Vertical units have side access only. Horizontal units have both side and bottom access.
On a horizontal unit, take the bottom access filter. Serviceability does not get easier than opening a panel and dropping the filter out the bottom. Changing a filter out the left or right side of a hung horizontal unit is meaningfully harder.
Large units (AE / AB) — why can't I pick MERV 8 or 13?
The big units do not offer the MERV filters themselves — they offer filter racks. Standard is a 1″ rack, with optional 2″ racks in two-sided (left or right) or four-sided (left, right, top and bottom) configurations. AB ships with a 4″ pleated filter bank standard.
Take one of the 2″ racks. If a 1″ rack lands on the job and the customer later wants a 2″ MERV 8, you cannot do it. The upgrade costs almost nothing at order time and is impossible afterward.
AE motor horsepower & orientation
Motor horsepower?
Depending on unit size you may have a couple of horsepowers to choose from; some sizes only offer one. If the schedule calls for more static, step up the horsepower where it is available.
Motor orientation — the most confusing field on the page?
99% of the time you pick standard blower and motor orientation. That covers essentially every unit ordered.
Rotate the blower 180° and you change the way air curls out of the unit — occasionally useful for optimal duct airflow in a special application.
Rotate the motor 180° and you change which side you service the motor from. That is what lets you set two units side by side, or push a unit up against a wall.
If you run into either of those applications, call the York Engineering Applications team — they have documents and photos and will hop on a call.
AE system control — VFD, DDC, and the near-VAV unit
What is the factory VFD?
An ABB 550 — probably the most common water source heat pump VFD in the market. Selecting it requires the inverter duty motor.
What does the DDC + VFD combination give me?
Selecting the option that pairs BACnet DDC with the VFD puts you 95% of the way to a VAV unit right from the factory. No extra lead time, no special program — all the logic already lives in the DDC controller.
You just need a Control Air M (HMI) on site to program it. Configuring the unit for a VAV application takes well under ten minutes.
Controls, Boards & DDC
UPM · ECM · options card · DDC · zone sensorsUnit mounted control
- LED display provides indication for unit operating mode as well as fan speed and fault indication
- Touch pad for temperature, fan and mode adjustment
- UPM is now included with the unit mounted controls, which brings:
- 5 minute anti short cycle timer
- Random start
- Intelligent reset
- 90 second low pressure bypass timer
Unit mounted control
UPM 2.0 board — terminal map
| # | Connection |
|---|---|
| 1 | Compressor Contact Output |
| 2 | Compressor Y1 Call |
| 3 | High Pressure Switch |
| 4 | Low Pressure Switch |
| 5 | Water Coil Freeze 1 |
| 6 | LED Status Diagnostic |
| 7 | Air Coil Freeze 2 |
| 8 | Condensate Overflow |
| 9 | Ground |
| 10 | UPM Settings Dip Switch |
| 11 | A2L Sensor Connection |
| 12 | 24VAC Power Common |
| 13 | 24VAC Power Input |
| 14 | UPM Standoff |
| 15 | Power LED |
| 16 | FAN |
| 17 | Dry Contact |
UPM 2.0 board
UPM fault codes & dip switches
Dip switch functions
| SW | Function | Description | Off (I) | On (O) |
|---|---|---|---|---|
| 1 | Lockout | The number of times a fault condition can occur in 60 minutes before the unit goes into a hard lockout. | 2 | 4 |
| 2 | Reset | Determines how a hard lockout can be reset. R requires the board to be manually powered off and back on to exit a hard lockout. Y means the lockout can be cleared from the thermostat. | Y | R |
| 3 | Alarm | Determines the alarm output signal. | PULSE ** | CONST |
| 4 | Test | Reduces all time-delay settings to 10 seconds during troubleshooting or verification of unit operation. * | No | Yes |
| 5 | Freeze 1 | Freeze limit trip should only be changed to 15°F when a closed loop system with an appropriate antifreeze mixture is used. | 25°F | 15°F |
| 6 | Freeze 2 | — | 25°F | 15°F |
| 7 | Pump | — | No | Yes |
Blink codes
| Blinks | Fault | Fault criteria |
|---|---|---|
| None | None | All fault conditions normal |
| 1 | High pressure | Refrigerant discharge pressure has exceeded 60 PSIG † |
| 2 | Low pressure | Refrigerant suction pressure has fallen below 40 PSIG |
| 3 | Water coil freeze | Refrigerant temperature to the water coil has fallen below 26°F for 30 seconds |
| 4 | Condensate overflow | Condensate levels in the unit drain pan are too high |
| 5 | Brown out | Control voltage has fallen below 18 VAC |
| 6 | Air coil freeze | Refrigerant temperature to the air coil has fallen below 26°F for 30 seconds |
ECM board — terminal map
| # | Function |
|---|---|
| 1 | Motor Harness Plug |
| 2 | Blower DDM Adjustment |
| 3 | Motor Settings |
| 4 | Dehumidification Indication |
| 5 | Thermostat Contact Inputs |
| 6 | DDM Count Indicator |
| 7 | Thermostat Input Status Indication |
| 8 | Reheat Digital Outputs |
| 9 | Thermostat Outputs |
| 10 | 24 VAC |
| 11 | Hot Gas Re-Heat Enable Switch |
ECM board
Options card — terminal map
| # | Feature |
|---|---|
| 1 | Cool Set Point Potentiometer (Economizer) |
| 2 | Heat Set Point Potentiometer (Boilerless Control) |
| 3 | Operating Mode Dip Switch |
| 4 | Entering Water Temperature |
| 5 | H Signal Input |
| 6 | O Signal Input |
| 7 | Y Call Input |
| 8 | LED Input Status |
| 9 | Economizer Output “E_OUT” |
| 10 | Hot Gas Reheat Output “H_OUT” |
| 11 | Boilerless Control Output “W_OUT” |
| 12 | Reversing Valve Output “O_OUT” |
| 13 | Options Card Standoff |
| 14 | LED Output Status |
| 15 | FAN Output “G_OUT” |
| 16 | Y Call Output “Y_OUT” |
| 17 | 24VAC Power Input |
| 18 | 24VAC Power Common |
Options card
Direct Digital Control (DDC)
What protocols does the DDC board speak?
The board is multi-protocol. It is BACnet as standard, and through dip switches on the board you can change it to Modbus or N2.
Is LON available?
No. LON has not been available for a couple of years now — ever since the major manufacturer of the LON cards went out of business. If a spec calls for LON, that conversation needs to happen early.
What do I need to order alongside DDC?
A 100 VA transformer (the DDC option is greyed out until you select it), your zone sensors, and — strongly recommended — at least one HMI per project.
DDC controllers
Control Air 5600, Control Air 5830, and Control Air 6120.
HMIs — pick one per project, not per unit
| HMI | How it connects | Reach | When to use it |
|---|---|---|---|
| Control Air M | RNET connection — the same connection the zone sensors use, on the left side of the DDC board. | One-to-one: one HMI to one water source heat pump. | The default recommendation. It works without BACnet, which is exactly the situation you are in at startup. |
| Control Air M+ | Requires a BACnet MS/TP connection. | Up to 50 water source heat pumps — auto-discover them all on the same BACnet connection. | Excellent once BACnet exists. Less useful at startup, because BACnet usually is not up yet. |
| Virtual Control Air M | A special cable that interfaces with the DDC board and ends in USB (you will usually need a USB-C adapter). Also connects to the bottom of a zone sensor. | Whatever you plug into — turns an Android phone or tablet into the HMI via an app from the Google Play Store. | Great to carry. Plug in and change heating/cooling, schedule, mode, inputs and outputs on the spot. |
Zone sensors — ZS Series R1
| Model family | What it does |
|---|---|
| ZS‑1 / ZS‑1H | Base — temperature reading only. |
| ZS‑1S | Slidebar — adds the ability to adjust temperature via a slidebar. |
| ZSP‑1 / ZSP‑1H / ZSP‑1HC | Push — temperature selection plus an LCD screen. |
| ZSM‑1 / ZSM‑1H / ZSM‑1HC | Manager — the most advanced. Fan mode on/off, heat mode, screen — options for essentially everything. |
Accessories
Hose kits · pump kits · thermostatsHose kits
How many options are there?
Six, ranging from a plain hose kit with a swivel all the way up through a hose kit with Y-strainer, blowdown valve and electric valve.
Someone just asked me for “a five ton replacement and a hose kit.” Which one?
At minimum, quote the hose kit with portable ball valve, swivel and one P/T port — the second option in the list. Two reasons:
- The ball valves let you do all of your circuit setting and isolate the unit. Old-school method of adjusting flow rate through a unit, and still very effective.
- The P/T (pressure & temperature) ports let you do all of your waterside commissioning and diagnostics.
Why do the P/T ports matter so much for diagnostics?
Because they let a technician calculate heat of rejection in the field. If you can measure flow rate (3 GPM per ton), entering and leaving water temperature (delta T — you want roughly 10°F in cooling), and leaving air temperature with a duct probe, you can compute heat of rejection and verify it against the tables in the IOM. If the numbers do not line up, that discrepancy is your diagnostic.
Ground loop pump kits
How do I know which one to select?
Refer to the York brochures — they include pump curves that let you size the kit by GPM. Whatever GPM you have sized to determines which pump you need.
Are these commercial or residential?
They are really more of a residential item, but York offers them for light-commercial-type applications too.
Thermostats
Is there a York thermostat in the selection software?
There is a thermostat category in the accessory dropdown, but no York-branded thermostat is set up in the software yet. As of the 8/14/26 webinar, York had just made a thermostat available at the factory but had not yet configured it in the system. It is being actively worked on.
What do I use instead?
On a DDC job you use zone sensors, not thermostats. On the residential split, the JDE air handler is compatible with most standard 24 VAC heat pump thermostats.
Warranty
Standard terms & extended optionsCommercial warranty
What do the extended warranties actually add?
Everything in the warranty dropdown is above and beyond the standard 5/1. When an option reads “2 to 5 years extended parts,” it means years 2, 3, 4 and 5 for parts — so adding it gives you a total of 5 years parts, 5 years compressor.
Can I add more than one?
No — only one warranty per unit. They nest inside each other: refrigerant circuit is included in parts, and parts is included in parts-and-labor. Stacking them would double-cover the same thing.
Do I get my multiplier on warranty?
No. All warranties are at net price. Equipment and accessories get the multiplier; warranties do not. This is also why the “weighted multiplier” on your quote summary looks strange — see the Quoting section.
Why did my warranty turn red when I changed the unit size?
Warranty is priced by unit size — bigger units have more expensive components, so a 4-ton warranty is a different line item than a 3-ton warranty. Change the size and the software flags the warranty for update. Remove it and re-add it.
Commercial warranty
Residential warranty
| Series | Warranty |
|---|---|
| QA | 1 year part warranty & 5 year compressor |
| QA in Florida | 5 years parts and 5 years compressor — Florida only |
| QD / QQ | 10 year part warranty & 10 year labor allowance |
Residential warranty
York Selection Software
Account → project → selection → ratingCommercial units are quoted, selected and ordered through the York selection software. Residential units are not in the software — they are handled outside it through price pages, with purchase orders submitted by email.
The homepage — what is actually on it
- News and technical updates — center of the page. Anything York needs reps to know gets posted here.
- Customer support contacts — right side. Parts team, tech support, and at the bottom the Engineering Applications team.
- Lead times — far right. Click where it says “Click here” to open commercial and residential lead times. Updated at a minimum once a week, and immediately if lead times change before that.
Creating a project
- Go to My Projects. Open an existing project with its Schedule button on the left, or type a new project name and click Add New.
- Fill in the project information page. Anything with a red star is mandatory. Project type, vertical market, and where the project sits in its phase (design/budget, bid, etc.).
- On the right, add any competing bids — JCI, ClimateMaster, Trane and so on — and set the basis of design. Remove any with the X.
- Bottom left, add the end customer. If you genuinely do not know who it is — a one-off replacement, a bid-stage job, a government project — pick one of the “unknown” options provided.
- Click Save. That takes you to the project schedule page, where you select equipment, create quotes, run performance, generate submittals and submit orders.
Selecting a unit
- On the project schedule, choose Select the product family → Commercial water-to-air heat pump.
- Pick your model from the list, then click Add New Line Item. That opens the pricing page.
- At the top, set the tag and quantity. Tag them individually (WSHP-1, WSHP-2, WSHP-3) or bump the quantity on one line — reps do it every way imaginable.
- Work down the base unit configuration: size → electrical → configuration (vertical/horizontal) → heat exchanger → water connections → return air → discharge air → fan motor → air coil. That gives you your base unit list price.
- Everything below that point — electrical options, cabinet construction, refrigerant circuit, transformer, system control, water flow control, waterside economizer, air filtration — is optional and additive.
- Add accessories and warranties through the Edit button and the accessory dropdown.
- Click Rate the unit to run performance.
Rating the unit — the performance page
What conditions does it default to?
The AHRI rating conditions — 85°F entering water, 3 GPM per ton. Every field on the page is adjustable; highlight a field to see the range you are allowed to enter.
Can I run glycol?
Yes — ethylene glycol, propylene glycol and methanol are all selectable.
How do I enter airflow?
It depends on which fan motor you selected:
- PSC — enter your CFM and pick low, medium or high blower speed.
- Constant torque ECM — five motor types (1 through 5). Some smaller units — roughly under 12 tons — only offer three.
- Constant airflow ECM — pick both your airflow and external static pressure, then click Calculate.
I do not know which blower speed to pick.
Two options. Click high and see what comes out, or click the small button to the left of “Airflow” to bring up the airflow tables — find your CFM and read across to the ESP you expect.
Important caveat: the airflow table is for a standard unit with no extra options. Adding a MERV 13 filter, hot gas reheat, or the waterside economizer adds pressure drop, so your final results may not match the table. Treat the table as a starting reference point, not the answer.
How do I know it worked?
A green success bar. If instead you get “airflow is out of range, please adjust your fan speed,” go back to the airflow table and increase your blower speed.
Building a whole schedule — the copy method
- Select and rate one unit completely, all the way through a successful performance run.
- Check that unit's box, make sure Select Action reads Copy, and create a copy.
- Open the copy with the dollar-sign / price icon and edit it: retag it, change the size, change the return air, change vertical to horizontal — whatever this unit needs.
- Click Rate the unit and enter the new CFM. Repeat for each line.
1. Warranty. Bigger units have more expensive components, so the warranty line is different. Remove it and re-add it.
2. Hose kits. They are sized to the water connection, so if the unit size changed the connection size may have too. Anything flagged red needs updating.
And while you are in there: remove the duplicated Control Air M. You need one per project, not one per unit — otherwise the project gets very expensive very quietly.
Quoting
Quote number → freight → multiplier → printCreating the quote
- On the project schedule, select all the equipment — check each box or use Select All — then choose Select Action → Quote.
- The quote worksheet opens with a unique quote number at the top.
- Set your expected close date, and on the shipping section your expected ship date.
- Pick the state. This is the single most important field on the page — picking the state is what populates the freight cost.
- Rep information and your sales manager pull in automatically. Review the equipment summary below.
Multipliers, markups and the weird “weighted multiplier”
Why does the weighted multiplier look wrong?
Because warranties are net-priced — no multiplier applies to them — while equipment and accessories do get your multiplier. Blending those together produces a weighted number that will not match your true equipment multiplier.
Ignore the weighted multiplier. To see your real number, scroll to Multipliers, Markups and Commissions.
How do I ask for a better multiplier?
In the multipliers section, type the multiplier you want, click Request Special Discount, fill out the required information, and click Request.
Can I put my markup in the system?
Yes. There is a markup field where you can enter your markup and see your resulting profit. Plenty of reps do this outside the system instead — both work — but it is there if you want the quote to carry it.
Is the probability percentage at the top right my markup?
No. That percentage (25%, for example) is quote-activity reporting. It tells York what phase and probability your projects sit at, which builds the pipeline forecast so the factory can plan materials and lead times. It has nothing to do with pricing.
Printing the quote — two versions
| Version | Markup applied? | What the customer sees |
|---|---|---|
| York quote | No — net price | Displays your multiplier and a full line-by-line pricing breakdown of all options. Internal / distributor-facing. |
| Quote to end customer | Yes — markup included | Markup is baked in, freight shown, one total price. No line-by-line breakdown, no multiplier. |
Submittals
Two clicks, two tabsGenerating submittals
- Open the project from My Projects using the Schedule button.
- Click the Submittal button at the top, then Generate Submittal.
- Two tabs open. Tab one is the water-to-air schedule. Tab two is the as-built submittal.
- Export either one to Excel, PDF or Word using the floppy disk icon at the top.
Ordering
The part people get wrongPlacing the order
- Always create the order from the quotation. Go back into the project, open the quote, scroll to the bottom and click Create Order. Doing it this way is what carries any special multipliers and quote information onto the order.
- The order worksheet opens with a unique order number — like the quote number, never reproduced, and gone if you delete the order.
- Enter your purchase order number and confirm the customer account number (most accounts default this in automatically).
- Fill in everything marked red, then the full shipping information and a contact name.
- Use special order instructions for anything the driver or warehouse needs — “call Joe Smith 48 hours before delivery, here is the number.”
- Give the whole order a once-over. Confirm your multiplier is still showing under Multipliers and Markups.
- Attach your purchase order. Select the file, set documentation type to Purchase Order, and click Upload. A green success bar means it worked.
- Scroll all the way to the bottom, click SUBMIT ORDER, then click YES.
“If you take one thing away…” — what happens after you submit
- You get a notification from the software confirming the order was submitted. If you do not get that notification, you probably did not submit the order. This is check number one.
- Customer service processes it. Give them 48 to 72 hours — they are a busy team.
- Orders over $50,000 come back to you for a signed acknowledgment — initialing all the pages of the order. Under $50,000, skip to the next step.
- The order is released to the factory, and customer service sends you an order confirmation, typically including an estimated ship date.
“Open” = you have NOT submitted it. Scroll to the bottom and click Submit Order.
Anything else — Submitted, Finalized, In Process — means it is being worked on.
Vendor / account numbers
Which vendor number do I use?
This is a sales-manager question rather than an engineering one — reach out to your York sales manager. If you are not sure who that is, email the Engineering Applications address and they will connect you with the right people.
In most cases your software account is already set up with your account number as a default, so it pulls into the order automatically.
Rep FAQ
Real questions, short answersEvery answer here also lives somewhere above with more context — this is the fast lane when a customer is on the phone.
Product & configuration
Who actually builds the York WaterSource units?
Florida Heat Pump (FHP). The product line presentation is a joint York/Bosch deck.
What refrigerant?
R‑454B across the entire portfolio — low GWP, and an A2L (mildly flammable), which is why leak detection appears throughout the options.
If I only learn two models, which two?
AA (½–6 ton) and AE (6–30 ton). Between them they are roughly 85–90% of everything a rep quotes — and almost everything else in the line is easier to select than those two.
What is the difference between straight-through and end-blow on a horizontal unit?
Straight through cuts a straight line from return to supply across the narrow path of the unit. End blow brings air in the side, turns it 90°, and discharges out the skinny end opposite the control box.
Can I convert discharge in the field?
Yes, on horizontal units. About nine steps, well laid out in the IOM, roughly ten minutes — swap panels and rotate the blower. If you stock straight-through units you can serve end-blow jobs from the same stock.
What does “front of the unit” mean?
The side where you access the electrical box. Every left/right/front/rear callout builds off that.
Copper or cupronickel?
Copper 90–95% of the time on commercial. Cupronickel only for open loop — pump-and-dump or open-loop geothermal where water quality is not maintained.
Do the units come standard with refrigerant leak sensors?
Over 64 oz / 4 lb of refrigerant, code requires it. Below that it is optional. AD and AQ at 5 and 6 tons (~80 oz) require it and the software forces the selection. On AE and AB it is standard. Rule: if you see it in the options list it is optional; if you cannot find it at all it is standard.
The equipment room door is 36″. What can I sell?
AE vertical with take-apart construction (up through 30 ton) — but the field has to braze, reconnect and recharge it. Or AB, where heavy-duty modular construction is standard and the refrigerant circuits stay pre-charged and sealed.
Which units are geothermal ready?
AA has extended range (geothermal) standard. AK and the AZ/QZ split are listed as geothermal ready. For open-loop geothermal, remember to move to cupronickel.
Which units are ENERGY STAR rated?
Residential QD, QQ, QZ Split and QW. QA is not.
Which series offer a counterflow cabinet?
AD (commercial) and QD (residential).
Which units offer the heat recovery package?
AD, AQ and QD on sizes 024–070. QQ on all sizes. On the water-to-water side, AH units only.
Can I get a painted cabinet?
Yes — an optional coated / painted cabinet is available for all commercial series. Coated/painted cabinet is standard across the residential line.
Options & pricing traps
Why is my unit so expensive?
Almost always over-selection. Work down the Option Guide above and remove anything the job does not actually need — the most common offenders are a duplicated HMI on every line, an unnecessary cupronickel upgrade, and warranty stacked on a unit that did not need it.
Why can't I select DDC?
You need the 100 VA transformer first. Same for the waterside economizer. Change the transformer and the option becomes selectable.
The spec calls for LON. Can I get it?
No. LON has not been available for a couple of years — the major LON card manufacturer went out of business. The board is BACnet standard, with Modbus and N2 available via dip switches.
460V three phase — anything I need to watch?
Yes. 460/3φ with the constant airflow ECM requires a neutral wire in the building. If there is no neutral, specify the constant torque ECM instead.
Can I put a two-way valve on the unit and on the hose kit?
No. One or the other. Both and the valves fight each other, full flow never establishes, and the unit trips a safety — no flow, low pressure or high pressure.
Customer only needs cooling. Should I quote cooling-only?
Be careful — cooling-only removes the reversing valve and that unit can never heat. Adding it back later means cutting into the refrigerant piping, evacuating and re-brazing. When in doubt, quote a standard heat pump and jump out the heating call. Reversing valve failure rates are extremely low.
Does the filter rack size really matter?
Yes, on AE and AB. A 1″ rack cannot later accept a 2″ MERV 8. Take one of the 2″ racks — it is cheap at order time and impossible afterward.
Is the flow proving switch worth the money?
On schools, high-rises and large commercial, it is arguably the best value in the option list. It auto-resets — without it, a no-flow start hard-locks the unit and somebody has to physically go reset it.
Do I get my multiplier on warranties?
No. Warranties are net-priced. Equipment and accessories get the multiplier.
Can I add more than one warranty to a unit?
No — only one. They nest: refrigerant circuit is included in parts, and parts is included in parts-and-labor.
What does “2 to 5 years extended parts” actually mean?
Years 2, 3, 4 and 5 for parts. Added to the standard 1-year, you end up with 5 years parts and 5 years compressor.
Software, quoting & ordering
Can I quote residential in the software?
No — commercial only. Residential is quoted from price pages and ordered by emailing the PO. York has said residential may be added for quotation purposes later.
Where do I find lead times?
On the software homepage, far right — click where it says “Click here.” It opens both commercial and residential lead times, updated at minimum weekly.
My quote has no freight cost. Why?
You did not pick the state on the shipping section. That is the field that populates freight.
The weighted multiplier on my quote looks wrong.
It is skewed by the net-priced warranties. Ignore it and read your real number under Multipliers, Markups and Commissions.
What is the 25% at the top right of my quote?
Quote-activity probability for York's pipeline reporting — it helps the factory plan materials. It is not your markup.
I clicked Generate Submittal and nothing happened.
Pop-ups are blocked. Look for the notification or a red slash on a browser icon and allow pop-ups for the site. Engineering Applications has per-browser instructions if IT is in the way.
Should I create the order from the quote or start fresh?
Always from the quotation. That is what carries your special multipliers and quote information onto the order.
How do I know my order actually went through?
Two checks. (1) You should get a notification from the software. (2) Open the order — if the status reads “Open,” it was never submitted. Anything else means it is being worked.
What happens on an order over $50,000?
Customer service comes back to you for a signed acknowledgment — initialing all pages of the order — before it releases to the factory.
My PO won't upload.
Some special characters are rejected — parentheses are one. Rename the file. Also switch the file-type filter to All Types if the PDF is not showing in the picker.
“Some of the accessories are not valid based on your configuration.”
Normal when you copy a line and change the size. The warranty is priced by unit size and the hose kit is sized to the water connection. Anything red needs to be removed and re-added.
“Airflow is out of range, please adjust your fan speed.”
Open the airflow tables (the button left of Airflow) and step the blower speed up. Remember the tables assume a standard unit — MERV 13, hot gas reheat and the waterside economizer all add pressure drop.
A field is greyed out and I can't figure out why.
Click the small blue circle next to it. That clears the dependencies and resets the downstream selections so you can choose again.
I deleted a quote by mistake. Can I get the number back?
No. Quote and order numbers are unique and never reproduced. Once the quote or order is deleted, that number is gone permanently.
Who to Call
And what to send themYork support routing
| Ask | Who | Where to find them |
|---|---|---|
| Selection won't work · software issue · controls question · product question · refrigerant combination not in the software · rotated motor applications · browser pop-up instructions | Engineering Applications | Software homepage, bottom of the customer support contacts panel on the right |
| Field troubleshooting and diagnostics | Tech Support | Software homepage, customer support contacts |
| Replacement parts | Parts Team | Software homepage, customer support contacts |
| Order status · acknowledgment · order confirmation · ship dates | Customer Service | They contact you after submission; escalate through your sales manager if you hear nothing in a few days |
| Vendor / account numbers · multiplier and commercial terms | Your York Sales Manager | Pulls in automatically on your quote; Engineering Applications can connect you if you are unsure |
No matches.
Try a shorter term, or check the spelling — the search matches all words you type.